Electrical Systems & Switchboards

Main and emergency switchboards, distribution boards, motor control centres, transformers and cabling.

Busbar arrangement, clearances and torque marks1Breaker ratings and protection settings2Wiring workmanship and labelling3Interlocks and synchronising functions4Insulation resistance and high-voltage test5
Illustrative process visualization

Switchboards are engineered to order. Inspection confirms that the build follows the approved drawings, that components are rated for the fault level and marine environment, and that protection settings and interlocks work as designed.

Inspection checkpoints

The numbers correspond to the checkpoints marked in the diagram above. Select a point in the diagram to jump to its explanation.

  1. Busbar arrangement, clearances and torque marksBusbar size and support spacing are compared with the short-circuit calculation. Clearance and creepage distances are measured, and bolted joints are checked for torque marking.
  2. Breaker ratings and protection settingsEach breaker is checked for frame size, breaking capacity and trip unit. Protection settings are compared with the selectivity study, and trips are proven by secondary injection where specified.
  3. Wiring workmanship and labellingWiring is examined for correct cross-section, ferrules, bending radius, segregation of power and control circuits, and labels that match the diagrams. Good workmanship here saves days during commissioning.
  4. Interlocks and synchronising functionsMechanical and electrical interlocks are tried to confirm that prohibited switching is impossible. Synchronising, load sharing and automatic changeover are demonstrated with the test supplies available at the maker.
  5. Insulation resistance and high-voltage testInsulation resistance is measured between phases and to earth, before and after the high-voltage withstand test. The values are recorded as the reference for later tests on board.

Typical documentation

Single-line diagram, short-circuit and selectivity study, wiring diagrams, FAT report, component type approvals.