HVAC & Auxiliary Systems
Air handling units, chillers, fans, ducting, refrigeration and other auxiliary plant.
HVAC performance is decided by capacity calculations, duct installation quality and commissioning balance. On yachts it is also a noise and comfort question; on commercial vessels fire dampers and ventilation shutdowns carry safety functions.
Inspection checkpoints
The numbers correspond to the checkpoints marked in the diagram above. Select a point in the diagram to jump to its explanation.
- Unit build and coil pressure testUnits are compared with the data sheet for casing, coils, fans and filters. Coils are pressure tested, and drain pans, access doors and insulation are checked.
- Fan performance and vibrationAir flow and static pressure are measured and compared with the fan curve. Vibration and noise are recorded, and belt drives and anti-vibration mounts are inspected.
- Duct tightness and insulationDuct joints and penetrations are examined, and leakage is tested where a tightness class is specified. Insulation thickness, vapour barrier and fire insulation at boundaries are checked.
- Damper operation and indicationFire and shut-off dampers are operated locally and remotely. Closing on release, the indication on the control panel and access for inspection are verified.
- Air balance and capacity verificationAir quantities are measured at the outlets and adjusted to the design values. Cooling and heating capacity are checked by temperature measurements under the conditions available.
Typical documentation
Heat load calculation, equipment data sheets, pressure and leak test records, commissioning and air-balance reports.